Short answer: backup power costs two to four times what grid power costs, and the cheapest source is not the one most people assume. Running a portable generator on gasoline delivers electricity at about 37 cents per kWh. Propane costs about 58 cents. A natural gas standby generator is the cheapest fuel at about 19 cents, close to the grid itself. A lithium battery, spread over its rated cycle life, works out to 15 to 27 cents per kWh, but only if you actually cycle it thousands of times, which almost no backup-only owner ever does. The tables below show the arithmetic behind each figure so you can substitute your own fuel prices.
The Fuel Cost Table
Every fuel carries a fixed amount of chemical energy, and a generator converts a fraction of it into electricity. Small air-cooled engines are not efficient machines: 22 to 30 percent of the fuel’s energy reaches the outlet, and the rest leaves as heat and noise. Combining the energy content, the conversion efficiency and current US retail prices gives the cost per delivered kWh.
| Fuel | Energy content | Typical engine efficiency | kWh delivered per unit | Assumed price | Cost per kWh |
|---|---|---|---|---|---|
| Gasoline | 33.7 kWh per gallon | 25% | 8.4 | $3.10 per gallon | $0.37 |
| Propane | 26.8 kWh per gallon | 23% | 6.2 | $3.60 per gallon | $0.58 |
| Natural gas | 29.3 kWh per therm | 24% | 7.0 | $1.35 per therm | $0.19 |
| Diesel | 37.9 kWh per gallon | 30% | 11.4 | $3.90 per gallon | $0.34 |
| Grid electricity, for reference | n/a | n/a | n/a | US residential average | $0.16 |
Substitute your own prices with this formula:
Cost per kWh = fuel price per unit / (energy content per unit x engine efficiency)
Propane looks expensive here, and it is, per kWh. It carries about 27 percent less energy per gallon than gasoline while usually costing more at the pump. What propane buys instead is storage: it does not go stale, does not gum a carburetor, and can sit in a tank for a decade. That tradeoff, not the price per kWh, is the real argument, and we go through it in natural gas vs propane generators.
The Battery Table
A battery buys no fuel, so its cost per kWh is the purchase price spread over the energy it will deliver in its lifetime. Divide the price by (rated cycles x usable kWh).
| Equipment | Typical price | Usable kWh | Rated cycles to 80% | Lifetime kWh | Cost per kWh |
|---|---|---|---|---|---|
| 1 kWh portable station, LiFePO4 | $799 | 1.0 | 3,000 | 3,000 | $0.27 |
| 2 kWh portable station, LiFePO4 | $1,499 | 2.0 | 3,000 | 6,000 | $0.25 |
| 5 kWh home battery | $6,500 installed | 5.0 | 6,000 | 30,000 | $0.22 |
| 13.5 kWh home battery | $12,000 installed | 13.5 | 6,000 | 81,000 | $0.15 |
Those numbers look competitive with grid power, and for a solar household that cycles the battery daily they genuinely are. For a backup-only household they are fiction. A battery bought purely for outages might see 20 cycles in ten years, not 3,000. At 20 cycles, that $799 1 kWh station delivers 20 kWh across its useful life, which is $40 per kWh. The battery’s per-kWh cost only falls to the table’s figure if you use it, which is why the strongest financial case for a home battery involves solar or time-of-use rate arbitrage rather than outages alone. The full breakdown is in is a home battery worth it without solar.
What One Day of Backup Actually Costs
Using the essentials profile of 6 kWh a day, fuel only:
| Source | Fuel used for 6 kWh | Fuel cost for one day | Fuel cost for a 3-day outage |
|---|---|---|---|
| Gasoline portable | 0.7 gallons | $2.21 | $6.63 |
| Propane portable | 1.0 gallons (about 1/5 of a 20 lb tank) | $3.50 | $10.50 |
| Natural gas standby | 0.9 therms | $1.15 | $3.45 |
| Diesel portable | 0.5 gallons | $2.06 | $6.18 |
Two things jump out. First, fuel for a realistic outage is cheap. A three-day blackout on essentials costs less than a restaurant meal. Second, that is not how anyone actually runs a generator. Most people do not meter their load down to 6 kWh a day; they start the generator in the morning and let it idle at 20 percent load all day, which burns two to three times the fuel for the same delivered energy. A generator at 25 percent load is dramatically less efficient per kWh than one at 50 to 75 percent. Running the right size unit near its sweet spot is the single biggest lever on real-world cost, and it is the main argument for inverter models that throttle the engine to the load, covered in inverter vs conventional generators.
The Cost Nobody Counts: Equipment Over Its Life
Fuel is the visible number. The equipment is the bigger one. Spread the purchase over ten years and a realistic number of outage hours:
| Setup | Purchase and install | Maintenance over 10 years | 10-year total | Cost per outage day covered |
|---|---|---|---|---|
| 1 kWh power station | $799 | $0 | $799 | $40 to $80 |
| 4,500 W dual fuel portable | $900 | $250 oil, plugs, filters, stabilizer | $1,150 | $38 to $58 |
| 22 kW natural gas standby | $12,000 with transfer switch | $2,500 annual service | $14,500 | $480 to $725 |
| 13.5 kWh home battery | $12,000 | $0 | $12,000 | $400 to $600 |
The per-day figures assume 20 to 30 outage days across the decade, which matches the federal reliability data for a moderately storm-prone state. In a place that averages one short outage a year, divide the ten-year total by ten days and the standby generator costs well over a thousand dollars per day of use. That is not an argument against buying one. It is an argument for being honest that a whole-house standby unit is bought for comfort and continuity, not for cost efficiency, the same way a second car is. The break-even reasoning is in whole-house generator cost.
Where Solar Changes the Math
A solar panel has no fuel cost and no cycle limit that matters on this timescale. A 200 W portable panel costs $300 to $500 and returns 0.6 to 1.0 kWh on a clear day. Over ten years of summer use that is several hundred kWh, landing somewhere near 10 to 20 cents per kWh, and it is the only source in this article whose marginal cost is zero once installed.
The catch is rate, not cost. A 200 W panel takes six to eight hours to put one kWh into a battery, so solar refills slowly and cannot carry a load directly. Its correct role in a backup system is extending a battery’s endurance across a multi-day outage rather than acting as a power source in its own right. Panel sizing and placement are covered in best solar panels for portable power stations.
How to Cut the Cost of Backup Power
- Size the generator to the load. An oversized unit idling at 20 percent load wastes fuel on every kWh. Most homes need far less than they buy.
- Run in blocks, not continuously. Four hours on, four off keeps a refrigerator and freezer safe and halves fuel use. Food safety timing is in keeping food safe during a power outage.
- Never use resistance heat from a generator or battery. A 1,500 W space heater costs about 55 cents an hour in gasoline and will drain a 2 kWh battery in an hour. Propane heat rated for indoor use is an order of magnitude cheaper per BTU.
- Buy fuel before the storm. Prices rise and stations run dry, and stabilized gasoline stored properly keeps for a year. Storage rules are in how to store generator fuel at home.
- Maintain the engine. A dirty air filter or fouled plug can cut efficiency by 10 to 20 percent, which shows up directly in gallons burned. The schedule is in the portable generator maintenance checklist.
Frequently Asked Questions
Is it cheaper to run a generator or use grid power?
Grid power is cheaper in every case. The US residential average is about 16 cents per kWh against 19 cents for natural gas backup and 37 cents for gasoline. Backup power is insurance, not a savings device.
Which backup fuel is cheapest?
Natural gas, at roughly 19 cents per kWh, because it is the cheapest fuel per unit of energy and arrives by pipeline with no refueling. It requires a permanently installed standby generator and a gas line, so the cheap fuel comes attached to the most expensive equipment.
How much does it cost to run a generator for 24 hours?
At a realistic essentials load of 6 kWh a day, about $2.20 in gasoline. Running the same generator continuously at a light load without managing it, which is what most people do, costs $15 to $30 a day. The gap is load management, not the generator.
Are batteries cheaper than generators over time?
Only if you cycle them often. A battery used daily with solar delivers power at 15 to 27 cents per kWh. A battery used only for the occasional outage delivers a few dozen kWh over its whole life, which makes its effective cost per kWh enormous. Buy a battery for silence, instant switchover and indoor safety, not for cost.
Does running a generator at low load waste fuel?
Yes, substantially. Efficiency peaks between 50 and 75 percent of rated output. A conventional generator at 20 percent load can use nearly as much fuel per hour as at 60 percent while delivering a third of the energy. Inverter generators reduce the penalty by varying engine speed with demand.