Short answer: a typical American home needs about 10 kWh of usable battery to cover essentials for a full day, 20 to 30 kWh to run most of the house without air conditioning for two days, and 40 kWh or more per day if central AC has to keep running. One Tesla Powerwall 3 holds 13.5 kWh; one Enphase IQ Battery 5P holds 5 kWh. So the honest answer for most families is one to two large batteries for essentials, and a solar array or generator to recharge them if the outage runs past a day. The sizing chart below puts numbers on four backup profiles for one, two and three days, and the worksheet after it lets you build your own.
The Sizing Chart: Usable kWh Needed by Backup Profile
Figures are usable kWh, meaning what the battery can actually deliver, not the nameplate. They already include a 10 percent allowance for inverter and round-trip losses and a 15 percent safety margin, and they assume no recharge from solar or a generator during the outage. If you have solar, skip to the section on recharge, because it changes the answer dramatically.
| Backup profile | What runs | Daily use | 1 day | 2 days | 3 days | Continuous power needed |
|---|---|---|---|---|---|---|
| Essentials only | Refrigerator, freezer, LED lights, phones, laptops, router, a fan or CPAP, gas furnace blower a few hours | 5 to 7 kWh | 8 kWh | 16 kWh | 24 kWh | 2 to 3 kW |
| Partial home | Essentials plus well or sump pump, microwave, coffee maker, TV, garage door, gas furnace blower all night, window AC unit | 10 to 14 kWh | 16 kWh | 32 kWh | 48 kWh | 5 to 7 kW |
| Whole home, no central AC or electric heat | Everything above plus electric range, dishwasher, washer, electric water heater used sparingly | 18 to 25 kWh | 28 kWh | 56 kWh | 84 kWh | 8 to 10 kW |
| Whole home with central AC or heat pump | Everything, including a 3-ton central AC running 8 to 12 hours a day | 40 to 55 kWh | 60 kWh | 120 kWh | 180 kWh | 10 to 14 kW, plus compressor start surge |
The gap between the top and bottom rows is the whole story of home battery backup. Essentials for a day is a single battery. Whole-home comfort for three days is a small commercial installation, which is why almost nobody sizes a battery for that; they size for essentials and pair it with solar, a generator, or both.
How Many Batteries That Is
Translating kWh into hardware, using usable capacity per unit as published by each manufacturer:
| Battery unit | Usable kWh | Essentials, 1 day (8 kWh) | Partial home, 2 days (32 kWh) | Whole home no AC, 2 days (56 kWh) |
|---|---|---|---|---|
| Tesla Powerwall 3 | 13.5 | 1 | 3 | 5 |
| FranklinWH aPower 2 | 15 | 1 | 3 | 4 |
| Enphase IQ Battery 5P | 5 | 2 | 7 | 12 |
| Enphase IQ Battery 10C | 10 | 1 | 4 | 6 |
| Portable station, 3.6 kWh class | 3.1 | 3 | 11 | 18 |
Units are rounded up because you cannot install half a battery. Notice how quickly the partial-home and whole-home columns run into stacks of four to twelve units. At current installed prices that is well into the tens of thousands of dollars, which is where the math in how much home battery backup costs starts to favor a standby generator for anything beyond essentials.
The Worksheet: Size Your Own in Four Steps
Step 1. List what must run and for how many hours a day. Not what you would like to run; what you would be genuinely unsafe or miserable without. Use the reference table below for typical daily energy per load. If you own a plug-in meter, measure instead, especially the refrigerator and any pump.
| Load | Running watts | Typical hours per day in an outage | kWh per day |
|---|---|---|---|
| Full-size refrigerator | 100 to 200 (cycling) | 24, compressor on about 1/3 | 1.2 to 1.8 |
| Chest freezer | 80 to 150 (cycling) | 24, compressor on about 1/3 | 0.8 to 1.2 |
| LED lighting, whole house | 60 to 120 | 5 | 0.3 to 0.6 |
| Phones, laptops, router | 40 to 80 | 24 | 0.5 to 1.0 |
| CPAP without humidifier | 30 to 60 | 8 | 0.3 to 0.5 |
| Gas furnace blower | 400 to 800 | 6 to 10 (cycling) | 2.5 to 5.0 |
| Well pump, 1 HP | 1,000 to 1,500 | 1 to 2 | 1.0 to 2.5 |
| Sump pump, 1/2 HP, in a storm | 600 to 900 | 1 to 4 (cycling) | 0.5 to 2.5 |
| Microwave | 1,000 to 1,500 | 0.3 | 0.3 to 0.5 |
| Television, 55 inch | 80 to 150 | 4 | 0.3 to 0.6 |
| Window AC, 8,000 BTU | 700 to 1,000 | 8 | 5 to 8 |
| Electric water heater, 50 gal | 4,500 | 1 to 2 | 4.5 to 9 |
| Central AC, 3 ton | 3,000 to 4,000 | 8 to 12 (cycling) | 24 to 45 |
| Electric range, one meal | 2,000 to 3,000 | 1 | 2 to 3 |
| Space heater | 1,500 | 6 | 9 |
Step 2. Add the kWh per day column. This is your daily energy. For a family that lists fridge, freezer, lights, electronics, a CPAP and a few hours of furnace blower, the total lands between 5 and 8 kWh. That is the essentials row of the sizing chart.
Step 3. Multiply by the days you want to cover, then divide by 0.9 and add 15 percent. The division covers round-trip losses; the 15 percent is the margin for the load you forgot and the cold night that cuts capacity. For 6 kWh a day and two days: 12 / 0.9 = 13.3, plus 15 percent = about 15.3 kWh usable.
Step 4. Check the power, not just the energy. Add the running watts of everything that could be on at the same moment, then confirm the battery’s continuous output covers it and its surge rating covers the largest motor start. A well pump or central AC compressor can pull three to five times its running watts for a second when it starts. A single Powerwall 3 delivers 11.5 kW continuous, an Enphase 5P delivers 3.84 kW, and that difference decides whether the pump starts at all. This is the same logic used for generators, and the generator size calculator handles the motor-start math for either.
Why Recharge Changes Everything
Every number above assumes the battery starts full and nothing goes back in. Add solar and the picture flips. A 6 kW rooftop array in most of the United States produces 20 to 30 kWh on a clear day and 5 to 10 kWh on an overcast one. Even the bad day refills a 10 kWh battery halfway. That is why installers size batteries for one night, not three days, when solar is present: the battery only has to carry the house from sunset to sunrise, roughly 5 to 8 kWh for essentials, and the panels handle daytime.
Without solar, the recharge options during an outage are a generator or waiting for the grid. A battery paired with a small inverter generator is a strong combination: the generator runs a few hours to refill the battery and is then switched off, which stretches fuel and gives silent nights. We cover the case for batteries in homes with no panels in is a home battery worth it without solar.
Three Worked Examples
A two-bedroom home with gas heat and no medical equipment. Fridge, lights, electronics, furnace blower 6 hours in winter: about 5 kWh a day. Two days: 5 x 2 / 0.9 x 1.15 = 12.8 kWh. One Powerwall 3 or one aPower 2 covers it with a little margin; a 3.6 kWh portable station covers one night of the same loads if the furnace blower is left out.
A rural home on a well with a sump pump. Essentials 5 kWh, well pump 1.5 kWh, sump pump 1.5 kWh in a storm: 8 kWh a day. Two days: 20.4 kWh usable, so two Powerwalls or two aPower units. The bigger issue is the surge: a 1 HP well pump can need 4 to 6 kW to start, which rules out most portable stations and the smaller wall batteries. Details in well pump backup power.
A Gulf Coast home that must keep central AC running. Essentials 6 kWh plus AC 30 kWh: 36 kWh a day, 46 kWh usable for one day, 92 for two. That is four to seven large batteries for a single day. Almost every family in this position ends up with a standby generator for the AC and, at most, a single battery for quiet overnight essentials. See is a whole-house generator worth it for the comparison at that scale.
Common Sizing Mistakes
- Sizing from the electric bill. Your monthly kWh divided by 30 is your normal day, not your outage day. In an outage you will not run the dryer, the oven and the AC the way you do on a Tuesday. Size from the must-run list.
- Forgetting the furnace blower. Gas heat still needs electricity for the blower and controls, and in a winter outage it is often the largest load in the house.
- Ignoring the nameplate versus usable gap. Manufacturers publish usable capacity for most wall batteries, but portable stations advertise total watt-hours. A “3,600 Wh” station delivers about 3,100 Wh at the outlet.
- Buying energy when you needed power. A 20 kWh stack of low-output batteries still cannot start a well pump. Check kW and surge before kWh.
- Sizing for the three-day storm when you have solar. Panels turn a three-day problem into three one-night problems. Size for the night.
Frequently Asked Questions
How many kWh does a house use per day during an outage?
For essentials only, 5 to 7 kWh. For most of the house without air conditioning, 18 to 25 kWh. With central AC running, 40 kWh or more. Normal daily use for the average American home is about 29 kWh, but outage use is lower because most discretionary loads stay off.
Will one Powerwall run my whole house?
One Powerwall 3 will power essentials for a day or two and can run most of a house without central AC for roughly a day. It will not run central AC for a full day on its own. Its 11.5 kW continuous output starts most residential loads, so the limit is energy, not power.
How many kWh do I need to run central air conditioning on battery?
A 3-ton unit uses 24 to 45 kWh a day in hot weather. Plan on 40 kWh of usable battery per day, or three Powerwall 3 units, and expect that to be the single biggest driver of the whole system cost.
Is 10 kWh enough for backup?
Yes for a full day of essentials in most homes, and for one night of nearly everything except central AC and electric water heating. Paired with solar, 10 kWh is the most common residential size for exactly that reason.
Should I get a battery or a generator?
Battery for essentials, quiet operation and short outages, especially with solar. Generator for whole-home loads, multi-day outages and homes without panels. Many households end up with both. The full comparison, including cost per kWh delivered, is in power station vs generator vs solar battery.